Available Reserve Margin

Available Reserve Margin is defined as the difference between the total actual generation capacity during the summer peak demand period and the total generation at the time of maximum demand of the year. The actual generation capacity is the sum of the nominal capacities of individual generators less the sum of all permanent generator derations. The total generation at the time of maximum demand of the yeat includes the auxiliary power required by the power stations.

i.e.:

Available Reserve Margin (MW) = Α - Β

Available Reserve Margin (%) = (Α - Β) x 100 / Β

where

Α = Total Actual Generation Capacity during the summer peak demand period of th year (MW)

Β = Maximum generation recorded during the year (MW)

The Available Reserve Margin is given in the table below for the last decade (the Autoproducer "Vassilikos Cement Works" is included):

                                      YEAR ==>

2001

2002

2003

2004

2005

2006

2007

2008

2009

2010

2011

2012

2013

2014

Α (MW) = Actual Generation Capacity  during the summer peak demand period

950

950

953

953

945

1033

1075

1116

1264

1384

1495

1180

1430

1430

Β (MW) = Total Generation (Power Station Auxiliary Consumption included) at the instant of maximum system demand

689

775

776

821

856

907

1056

1010

1095

1148

1100

1010

840

910

Available Reserve Margin = (Α Β) MW

261

175

177

132

89

126

19

106

169

236

395

170

590

520

«Available Reserve Margin» = [(Α - Β) x 100 / Β] %

38%

23%

23%

16%

10%

14%

2%

10%

15%

21%

36%

17%

70%

57%

 

* More information about previous and future years are given in the table below

It is noted that the data provided is average data which has been checked by the Cyprus TSO to the extend required for its internal needs.  The Cyprus TSO is not liable and will not be held responsible for any errors or inaccuracies contained in the data provided under this section.

  

Download Related Documents/ Diagrams/ Images

The Available Reserve Margin for years 1999-2014 is depicted in the table. The nominal and actual generating unit capacities are shown.
 
© 2017 Copyright Transmission System Operator, Cyprus